| Output Voltage: |
350 Vdc at 85-230
Vac increasing linearly to 380 Vdc from 230-264 Vac. |
| Output Power: |
1600 W max. at
170-264 Vac1200 W max. at 95-264 Vac1000 W max. at 85-264 Vac |
| Input
Voltage/Current: |
85-264 Vac, 47-63
Hz, 15 A max., single phase |
| Auxiliary Output: |
+12 Vdc at 50 mA
max., can tolerate short circuit for up to 5 sec. |
| Power Factor: |
0.99 typical |
| Inrush Current: |
40 A max. |
| Efficiency: |
94% typical |
| Holdup Time: |
20 msec min. from
input power failure until AC OKsignal goes low, full load and
85-264 Vac |
| AC Fail Warning: |
5 msec continued
operation after AC OK signal drops |
| Output Ripple: |
18 V pk-pk max. |
| Turn-on Time: |
800 msec max. until
Load Enable signal goes high |
| Line Regulation: |
2% max. output
variation over full input range |
| Load Regulation: |
2% max. output
variation from no load to full load |
| Overvoltage
Protection: |
Output limited to
400 Vdc |
| Overload Protection: |
Input current
limited to 15 A rms |
| Thermal Protection: |
Internal shutdown
cycles automatically |
| Input Fuse: |
Internal one-pole
16A NTD fuse |
| Output Short
Protection: |
External fuses
required at dc-dc converters |
| Leakage Current: |
1.0 mA max. at 240
Vac |
| Hipot: |
2200 Vdc |